STANDARD DIN VDE 0276 – 604
1. CONDUCTOR
IEC 60228 VDE 0295 Class 1 or 2 Cu
2. INSULATION
DIN VDE 0207 XLPE 2X11
Core Colours
VDE 0293 (J) (JZ) (OZ)
3. INNER SHEATH
HF LSZH bedding
4. JACKET
LSZH HM4 Black
1. BENDING RADIUS
12 x cable diameter
2. WORKING VOLTAGE
0,6 / 1 KV
3. TEST VOLTAGE
3,5 KV
4. TEMP RANGE
Flex using -5 / +60 °C
Fixed using -30 / +70 °C
5.INSULATION RESISTANCE
min.5000 M Ω km
HALOGEN TEST
Degree of acidity of gases TS EN 50267-2-3
Amount of halogen acid gas TS EN 50267-2-1
Smoke density TS EN 50268-2
SPOLL SIZE: 100 / 500 / 1000 mt
NOTES
(J) : Coloured and green - yellow core
(JZ) : Black cores (numbered) + green-yellow core
(OZ) : Black cores (numbered)
N2XH-J Construction is conductors stranding in layers. These cables generally used in industry systems, power plants, road lighting, measuring as a control cable. These halogenfree cables generally used for crowded places like hotels, airports, shopping, malls, schools, plazas. With the halogenfree construction it has low smoke and zero halogen during fire.
The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC