STANDARD BS 5308
1. CONDUCTOR
IEC 60228 VDE 0295 Class 1,2,5 Cu
2. INSULATION
PE / XLPE
Core Colours
Black-Blue Numbered
3. SCREEN
Al foil SnCu drain wire
4. OVERALL SCREEN
Al foil
5. INNER SHATH
HF
6. ARMOUR
Galvanized steel braid wire armour
7. JACKET
HF Black or Blue
1. BENDING RADIUS
10 x cable diameter
2. WORKING VOLTAGE
300-500 V
3. TEST VOLTAGE
2 KV
4. TEMP RANGE
Flex using -5 / +50 °C
Fixed using -30 / +70 °C
5. INSULATION RESISTANCE
min.5 G Ω km
6. CAPACITANCE
0,5-0,75 mm2 – 75 pF/m 1,5 mm2 – 85 pF/m
NOTES
Insulation might be PE,XLPE
SPOOL SIZES: 300-500-1000 mt
RE-2Y(st)Y-PIMF-DW QH construction is conductors twisted pairs screened with Al foil, pairs stranding in layers, overall Al foil screen and steel braiding armour for heavy mechanical resistance. These cables generally used in measurement, control technology such as control rooms of industrial plants and power stations. The cables serves for transmission of analog and digital signals up to frequencies of approx. 10 kHz. Suitable for indoor, outdoor and underground use. These cables are halogen free.
The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC