STANDARD BS 5308
1. CONDUCTOR
IEC 60228 VDE 0295 Class 1,2,5 Cu
2. INSULATION
PE / XLPE
Core Colours: Black-Blue Numbered
3. OVERALL SCREEN
Al foil 0,50 mm2 + drain wire
4. INNER SHATH
PVC
5. OVERALL SCREEN – ARMOUR
Galvanized steel wire braid armour
6. JACKET
PVC YM1 Black or Blue
1. BENDING RADIUS
10 x cable diameter
2. WORKING VOLTAGE
300-500 V
3. TEST VOLTAGE
2 KV
4. TEMP RANGE
Flex using -5 / +50 °C
Fixed using -30 / +70 °C
5. INSULATION RESISTANCE
min.5 G Ω km
6. CAPACITANCE
0,5-0,75 mm2
NOTES
Insulation might be PVC, PE,XLPE
SPOOL SIZES: 300-500-1000 mt
RE-2Y(st)Y-P QY construction is conductors twisted pairs stranding in layers and overall Al foil screen and steel braiding armour for heavy mechanical resistance. These cables generally used in measurement, control technology such as control rooms of industrial plants and power stations. The cables serves for transmission of analog and digital signals up to frequencies of approx. 10 kHz. Suitable for indoor, outdoor and underground use.
The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC